Base load is the level of electricity a building never drops below, day or night. In a leisure centre it's pool pumps and air handling; in an office it's IT, lifts, fridges, emergency lighting and anything left on. Measure it, watch it month by month, and every kilowatt you remove saves about £2,190 a year at 25p/kWh.
How the analyser measures it
The analyser converts every valid half-hourly reading to kW and takes the level demand stays above 95% of the time (the 5th percentile). It doesn't use the single lowest reading, because a meter fault or a power cut would drag that down. Two views matter most:
- Base load by month. A step up that doesn't follow the weather means something started running and didn't stop. Check this chart on every building.
- Base load across the estate. Rank buildings by base load per square metre, or against similar buildings, to see which carry the most continuous load for their size.
What makes it up in council buildings
| Building | Typical continuous load | Often reducible |
|---|---|---|
| Leisure centres and pools | Filtration and circulation pumps, pool hall air handling and dehumidification | Pool covers and night setback, variable speed drives, lower night turnover where water quality allows |
| Civic offices | IT, comms rooms, lifts, emergency lighting, fridges | Floors left lit and ventilated, oversized server cooling, plant in hand |
| Schools | IT, kitchen fridges and freezers, security | Heating and ventilation in the holidays, IT left on |
| Libraries and community buildings | Small IT, security, fridges | Water heaters, lighting, heating on a 7-day timer |
| Depots | Security lighting, comms, compressors | Workshop heaters and compressors left on overnight |
How to cut it safely
- Walk the building when it's closed with whoever runs it. Note what's on in empty areas and plant rooms.
- Sort it into three lists: must run (safety, security, water hygiene, fridges), could run less (pumps, fans, lighting, IT cooling), and shouldn't be on.
- Switch off the third list first. It costs nothing.
- Then the "could run less" list: setbacks, variable speed drives, LED and sensors.
- Check base load by month afterwards. It should step down and stay down.
Never switch off fire, security, emergency lighting or water safety systems to save energy.
Base load and solar
Base load runs through every sunny afternoon, including weekends, so it soaks up solar output. That's why leisure centres and other long-hours buildings usually use nearly all of what a well-sized system generates, while a school closed for six weeks in summer uses less. The analyser's Solar tab estimates the share from your own profile. See sizing solar from half-hourly data.
Working out the saving
Multiply the kilowatts you remove by the hours they would have run and by your unit rate. A load running all year is 8,766 hours (the average year, allowing for leap years), so 1 kW is about £2,190 a year at 25p/kWh. A load that only runs while a building is closed is worth less: work out the closed hours from the calendar.
Questions people ask
What share of a building's electricity is base load?
It varies, so measure your own. In a leisure centre with a pool it is commonly more than half; in our made-up example it is 58%. In an office or school it is usually much less.
Why not use the lowest reading?
Because one odd half hour, such as a power cut or a meter fault, would drag it down. The 5th percentile is a level the building genuinely stays above.
What does 1 kW of base load cost?
About 8,766 kWh a year, or about £2,190 at 25p/kWh.