See the kind of results the analyser produces before you find your own meter data. This is a made-up council leisure centre with made-up readings.

Made-up example. The leisure centre and its meter readings are invented, so nothing here is a real council's result. Every figure is what the analyser reports for our example file, on the leisure centre preset, at an illustrative 25p/kWh and an agreed supply capacity of 250 kVA.

This made-up leisure centre, with a 25 metre pool, a learner pool, a sports hall, a gym and a cafe, used about 830,000 kWh of electricity in a year, costing about £207,000 at 25p/kWh. More than half of it (58%) is base load, the demand that never switches off, because pool pumps and pool hall air handling run around the clock. From September that base load stepped up by about 18 kW when the pool hall plant stopped setting back at night.

The year at a glance

One half-hourly meter, open 06:00 to 22:30 on weekdays and 07:00 to 20:00 at weekends, with 363 days of valid readings.

829,765 kWhelectricity a year, costing about £207,441
54.5 kWbase load across the year, 58% of all use
155.3 kWbusiest half hour, on a July evening in a hot spell
26%of all use happens while the centre is closed
Heatmap of the leisure centre year: a dark band through opening hours, darker weekday evenings, and nights that get darker from September
Every half hour of the year on one chart: one column per day, darker for higher demand. Nights stay fairly dark because the pool plant never stops. From early September they get darker and stay that way.

What the report shows

Base load trend

Base load stepped up in September

52.5 kW to 70.2 kW

Base load by month rose from 52.5 kW in August to 70.2 kW in September and stayed above 70 kW all winter. The heatmap shows the extra load only while the centre is closed. The analyser prices closed-hours use above its reference at about £12,400 a year.

What to check: the pool hall air handling night setback and the pool cover routine, after the summer controls work.

Capacity

Room for a 60 kW heat pump, not 90 kW

58 kW firm headroom

A July hot spell sets the year's peak, leaving 58 kW of constant headroom within a 10% margin. Tested over October to April only, a 60 kW heat pump fits (215 kVA of 225 usable); a 90 kW one goes over in 923 half hours on 149 days.

What to check: the agreed capacity on the bill, before any pool heat pump design goes further.

Solar

All of a well-sized system would be used

100% at 184 kWp

At UK average output, a 184 kWp system would generate about 165,000 kWh a year and the centre would use all of it, covering 20% of its electricity. At 276 kWp it would still use 94%.

What to check: usable roof and car park area, then open the solar calculator from the Solar tab.

The base load itself is separate from these: 54.5 kW running all year is about £119,000. In a pool, much of it has to run, but every kilowatt removed is worth about £2,190 a year at 25p/kWh.

What could actually be saved?

The figures are what each pattern costs now, not a promised saving. To turn them into one:

  1. Take the base load step to the operator and the BMS contractor and have the night setback and pool covers restored.
  2. Walk the building after closing with the duty manager and list what's running in empty areas.
  3. Change one thing at a time, so each change shows up clearly in the data.
  4. Compare matched weeks before and after with the analyser's before-and-after view, for a measured saving rather than an estimate.

For every figure explained step by step, read the leisure centre worked example. To understand your own results, see how the analyser works.

Ready to see your own results?

Load your half-hourly meter files. It takes a few minutes and the data stays on your computer.